Thermal Magnetic Adjustable MCCB with 3 Pole from 1000 A - 1600 A, 50 kA

With Adjustable both Thermal & Magnetic Settings having 50 kA Breaking Capacity with Ics = 75% of Icu

Range 1000 A - 1600 A, Icu/Ics-50/37.5 kA

Different Current Ratings provide selection option depending on varied load conditions.

Versions - 3P

Offered in Three Pole configuration and suitable for Three Phase system requirement.

Adjustable Thermal & Magnetic Settings with Pole wise Adjustability Feature

Overload Setting is Polewise Adjustable (70-100)% & Short Circuit Settings is also Polewise Adjustable (4-10)times of Rated Current.

MRP Rs.: ₹ ..000

Buy Now
Compact Size & Double Insulation

Compact Size & Double Insulation

Space saving in the Panel and has the conductive path insulated with double shield i.e. Cover & Facia

Suitable for Switch Disconnector Purpose

Suitable for Switch Disconnector Purpose

Can be used as an Isolator

Provision of Push to tip button

Provision of Push to tip button

It is an alternate means to Trip the Breaker and also helps in checking the health of the Breaker.

Uniform front Escutcheon plate

Uniform front Escutcheon plate

Common Door Cut-out Facility provided lending Uniformity

Positive dolly position indication

Positive dolly position indication

Depicts the ON/OFF status of the breaker

Suitable for DC application

Suitable for DC application

Offers choice of system usage

Wide range of accessories available

Wide range of accessories available

Allows precise monitoring & control of circuit with the help of varied Internal & External Accessories

Separate Main & Arching contacts

Separate Main & Arching contacts

Arching Contacts makes first and breaks last thereby lending longer life to the main contacts.

Technical Specification

basic features
standard conformity IS/ IEC 60947-2
rated operational voltage 500 V AC
rated insulation voltage 750 V AC
rated impulse voltage 8 kV
type of release Thermomagnetic
utilisation category A
rated frequency 50/60 Hz
ambient temp 400 °C (500 °C on request)
operating altitude 2000 m
humidity 0 - 90%
rating range 1000 A - 1600 A
type of release Adjustable Type
no. of poles Three
breaking capacity Icu = 50 kA, Ics = 75% of Icu

Demo Videos

HAVELLS SUPPORT

Customer Services
1800 11 0303,
1800 103 1313
Email-id
customercare[at]havells.com